제품특징
✓ A technology is applied to detect abnormalities by installing arc, partial discharge,
and temperature sensors inside the power distribution panel.
✓ When the detection unit identifies anomalies such as arc, partial discharge, or temperature rise,
it compares them with predefined thresholds and transmits alarms and fault prevention signals to the SCADA system.
✓ By monitoring the conductor surface temperature and arc at connection points,
the system prevents overheating accidents caused by loose connections or overloads.
✓ The receiver unit integrates and analyzes the collected data to detect early signs of failure,
enabling proactive prevention of malfunctions and defects in the power distribution panel.
✓ A 3D seismic and vibration isolation device is applied to reduce both vertical and horizontal vibrations.
✓ By implementing a 3D seismic isolation system, shocks caused by earthquakes are mitigated, thereby enhancing overall safety.
✓ To prevent functionality loss due to seismic impact,
bolt transfers with anti-drop caps are used to prevent bolt detachment during earthquakes.
✓ After an earthquake, the system returns to its original position, providing stable support for the power distribution panel.
Category
Unit
Extra High Voltage
High Voltage
Rated Voltage
kV
24 / 25.8
7.2 / 3.6
Nominal Voltage
kV
22.9
6.6 / 3.3
Rated Current
A
630, 1250, 2000
400, 630, 1250, 2000, 2500, 3150, 4000
Rated Frequency
Hz
50 or 60
50 or 60
Rated Short Time Current
kA
MAX. 25
MAX. 40
Power Frequency Withstand Voltage. 1 MIN
kV
50
20 / 16
Lighting Impulse Withstand Voltage.
kV
125
60 / 45
Rated Operating Voltage
V
DC110 or 125
DC110 or 125